Why is my heat pump freezing up in summer? In cooling mode a heat pump does an air conditioner's job, and the cold coil is the one inside the house. Natural Resources Canada (NRCan) says that in the cooling cycle the refrigerant "goes to the indoor coil, which acts as the evaporator." House moisture condenses on that coil and runs to a drain. If the coil drops below freezing, that water sets as ice instead, on the coil and sometimes along the larger insulated copper line. The usual causes are restricted airflow or a refrigerant leak. Either way, start at the thermostat: Cool to Off.
Summer ice or winter frost?
In heating season, outdoor frost is defrost doing its job
While the heat pump is heating, the outdoor coil is the cold one. NRCan explains that near or below freezing, moisture freezes on it and the heat pump switches into defrost mode to clear it. Trane calls the steam that can rise off the unit during defrost "perfectly normal." More on heat pump defrost cycles in our winter guide.
In cooling season, the ice starts indoors
On Cool the roles swap. Trane says outdoor coils on an AC unit are "unlikely to freeze in the summer," and a heat pump on Cool is working as one. Its heat pump cooling guide describes a frozen indoor coil this way: "You may see visible icing at the indoor unit, or on the refrigerant lines at the outdoor unit."
The line that ices is the fat one wrapped in foam. Lennox explains that the larger line carries cool gas, is insulated, and is commonly called the suction line. So summer ice at the outdoor unit has usually worked its way out along that line from a frozen coil indoors. It isn't a defrost fault.
Ductless heads
A ductless mini split heat pump keeps its evaporator coil, fan and filter in the indoor head, so that is where the ice forms. Trane says clogged head filters "can restrict airflow and cause a frozen evaporator coil," and that a frozen coil will eventually drip. If water running down the wall is what you noticed first, start with a mini split leaking water.
Switch it to Off, not to defrost
At the thermostat, go from Cool to Off. Trane is emphatic: "If you have a heat pump DO NOT switch to defrost mode if the indoor coil is frozen." Defrost mode only clears ice from the outdoor coil, the ice that builds while the heat pump is heating the house. It does nothing for the coil indoors.
Trane also warns against running with frozen coils, and against chipping at the ice, which can damage the coil and cause a refrigerant leak. Our AC article covers how to thaw a frozen coil and deal with the meltwater.
Why a heat pump freezes up while cooling
Restricted airflow
The coil stays above freezing only while enough warm house air crosses it. Trane says low airflow can freeze it. The restrictions to look for:
- A dirty filter. On a ducted system the indoor coil sits "in the air handler or a cabinet next to the furnace," in Trane's words. When it shares a furnace, it gets its air through the furnace filter, so that filter matters in July as much as January.
- Blocked returns and registers. Trane names blocked return vents, such as a couch or other furniture pushed against one. NRCan says to keep vents and registers clear of furniture and carpeting.
- A dirty indoor coil. Trane recommends professional maintenance over a DIY coil cleaning.
- A blower not moving enough air. NRCan's air conditioning guide lists dirty fans with dirty filters and coils as things that reduce airflow. On a furnace-paired system that fan is the furnace's own, so furnace blower problems show up as cooling problems too.
A refrigerant leak
Trane: "The only reason a heat pump would have low refrigerant is if there is a refrigerant leak." Carrier calls a frozen coil in summer "suspicious," and says low charge is "probably the reason your indoor coil has frozen."
Trane's warning signs: oily residue around the indoor coil, or hissing near either coil. Either means calling an HVAC professional.
Adding refrigerant without fixing the leak only postpones the next freeze. Testing and charging, Carrier says, "is a job for a qualified HVAC technician."
Thermostat and cool nights
Trane lists a faulty thermostat. Its example is a coil found frozen only in the morning, because the thermostat isn't shutting the system down as overnight temperatures fall. Calgary summer nights can turn cool after a hot afternoon, so a system left on Cool overnight is worth watching.
Safe checks before you call
- Thermostat mode. Off while there's ice. Not defrost.
- The filter. Once the coil has thawed, fit a new one the same size as the old. Your equipment's manual lists how often to change it.
- Registers and returns. Supply registers open, return grilles not blocked by furniture.
- Ductless head filters. Turn the unit off first, then clean the filters as your model's manual describes.
Stop there. Panels, wiring and anything on the refrigerant side are technician work.
When it needs a technician
- It freezes again with a clean filter and clear registers and returns. Carrier says that may mean a refrigerant leak.
- There's oily residue near the indoor coil, or hissing.
- Meltwater is overflowing at the furnace, air handler or ductless head.
- There's ice on the outdoor unit or its copper lines in summer.
For a leak, Carrier describes the professional fix as locating it, repairing it and recharging the system. A recharge on its own isn't a repair.
Call 587-834-3668. We price the repair before any work starts. Icing faults and refrigerant leaks, found and repaired rather than topped up, are on our heat pump repair list. We dispatch from both Calgary and Airdrie, and Airdrie homeowners will find local details on heat pump repair in Airdrie. Call and we'll tell you honestly when we can get there.